Amman South power plant is located 15 km from the capital Amman center. The plant site is located within a rural area. Amman South power plant comprises 2 gas turbine generating units, each nominally rated at 30 MW gross. |
| Rated capacity (MW) |
60 |
| Fuel used | Diesel oil |
| Cooling | Dry cooling fans |
Components of Amman South Power Plant
Gas Turbines
|
Unit
|
Rated Capacity (MW el)
|
Fuel (HFO, LFO, NG)
|
Installation (Year)
|
Manufacturer Name
|
Type Name
|
|
GT 8
|
30
|
LFO |
1984
|
Hitachi
|
MS-6001B
|
|
GT 9
|
30
|
LFO |
1995
|
EGT (GE)
|
PG-6541B
|
Electrical Generators
|
Unit
|
Capacity (MVA)
|
Voltage (kV)
|
Installation (Year)
|
Manufacturer Name
|
Type Name
|
|
GT 8
|
37.87
|
11
|
1984
|
Hitachi
|
EFLA
|
|
GT 9
|
47.25
|
11
|
1995
|
GEC-Alsthom
|
T190-240
|
Generator Transformer
|
Unit
|
Capacity (MVA)
|
Voltage (kV/kV)
|
Installation (Year)
|
Manufacturer Name
|
Type Name
|
|
GT 8
|
42
|
11/33
|
1984
|
Hitachi
|
ONAF
|
|
GT 9
|
45
|
11/33
|
1995
|
Pauwels
|
ONAF
|
Accumulated Statistics in (2012)
|
Unit
|
Generated energy
|
Consumed energy
|
Sent out energy
|
Fuel Consumption
|
Running hours
|
|
(MWh)
|
(MWh)
|
(MWh)
|
(GJ)
|
(hr)
|
|
|
GT 8
|
18,314 | 275.964 | 18,038 | 270,793 | 22,938 |
|
GT 9
|
24,380 | 436.8 | 23,943 | 337,957 | 23,407 |
|
Total
|
42,694 | 712.76 | 41,981 | 608,749 | - |
Performance Indicators in (2012)
|
Unit
|
Availability (%)
|
Unplanned outage Factor (%)
|
planned outage Factor (%)
|
Efficiency (%) Sent out
|
Heat rate (KJ/kWh)
Sent out
|
|
GT 8
|
98.77 | 0.29 | 0.94 | 23.98 | 15,012 |
|
GT 9
|
99.73 | 0.27 | 0.00 | 25.50 | 14,115 |
|
Total
|
99.27 | 0.28 | 0.45 | 24.83 | 14,501 |