Hussein power plant is located in the northern region of Jordan, approximately 30 km northeast of the capital Amman. The plant site is located within Zarqa Industrial area and is situated 560 m above sea level. Hussein power plant comprises 7 generating units, 3 of which are steam turbines, nominally rated at 33 MW gross, 4 are steam turbines rated at 66 MW gross. |
| Rated capacity(MW) |
363 |
|
Fuel used |
Heavy fuel oil & diesel oil |
|
Steam condensing & cooling method |
Air condenser fans |
Components of HTPS Steam units
Boilers
|
Unit
|
Rated Capacity (MW el)
|
Fuel (HFO, LFO, NG)
|
Installation (Year)
|
Manufacturer Name
|
Type Name
|
|
Unit 1
|
33
|
HFO
|
1977
|
Breda
|
BD P.M
|
|
Unit 2
|
33
|
HFO
|
1977
|
Breda
|
BD P.M
|
|
Unit 3
|
33
|
HFO
|
1978
|
Breda
|
BD P.M
|
|
Unit 4
|
66
|
HFO
|
1980
|
Kawasaki
|
KR-300 |
|
Unit 5
|
66
|
HFO
|
1980
|
Kawasaki
|
KR-300
|
| Unit 6 | 66 |
HFO
|
1981 | Kawasaki |
KR-300
|
| Unit 7 | 66 |
HFO
|
1984 | Kawasaki |
KR-300
|
Steam Turbines
|
Unit
|
Capacity (MW el)
|
Installation (Year)
|
Manufacturer Name
|
Type Name
|
|
Unit 1
|
33
|
1977
|
Debritto
|
NA 3003 |
|
Unit 2
|
33
|
1977
|
Debritto
|
NA 3003 |
|
Unit 3
|
33
|
1978
|
Debritto
|
NA 3003
|
|
Unit 4
|
66
|
1980
|
Fuji
|
Single Casing Condensing |
|
Unit 5
|
66
|
1980
|
Fuji
|
Single Casing Condensing
|
| Unit 6 | 66 | 1981 | Fuji |
Single Casing Condensing
|
| Unit 7 | 66 | 1984 | Fuji |
Single Casing Condensing
|
Electrical Generators
|
Unit
|
Capacity (MVA)
|
Voltage (kV)
|
Installation (Year)
|
Manufacturer Name
|
Type Name
|
|
Unit 1
|
38.83
|
13.8
|
1975
|
Brown Bovery
|
WT16L052LL3
|
|
Unit 2
|
38.83
|
13.8
|
1975
|
Brown Bovery
|
WT16L052LL3
|
|
Unit 3
|
38.83
|
13.8
|
1977
|
Brown Bovery
|
WT16L052LL3
|
|
Unit 4
|
77.65
|
13.8
|
1980
|
Fuji
|
FTLR1521/63-2 |
|
Unit 5
|
77.65
|
13.8
|
1980
|
Fuji
|
FTLR1521/63-2
|
| Unit 6 | 77.65 |
13.8
|
1981 | Fuji |
FTLR1521/63-2
|
| Unit 7 | 77.65 |
13.8
|
1984 | Fuji |
FTLR1521/63-2
|
Generator Transformer
|
Unit
|
Capacity (MVA)
|
Voltage (kV/kV)
|
Installation (Year)
|
Manufacturer Name
|
Type Name
|
|
Unit 1
|
40
|
13.8/132
|
1974
|
Brown Bovery
|
ONAF
|
|
Unit 2
|
40
|
13.8/132
|
1974
|
Brown Bovery
|
ONAF
|
|
Unit 3
|
40
|
13.8/132
|
1977
|
Brown Bovery
|
ONAF
|
|
Unit 4
|
80
|
13.8/132
|
1980
|
Fuji
|
ONAF |
|
Unit 5
|
80
|
13.8/132
|
1980
|
Fuji
|
ONAF
|
| Unit 6 | 80 |
13.8/132
|
1981 | Fuji |
ONAF
|
| Unit 7 | 80 |
13.8/132
|
1983 | Fuji |
ONAF
|
Accumulated Statistics in (2012)
| Unit |
Generated energy
|
Consumed energy
|
Sent out energy
|
Fuel Consumption
|
Running hours
|
|
(MWh)
|
(MWh)
|
(MWh)
|
(GJ)
|
(hr)
|
|
|
Unit 1
|
52,792 | 5,036 | 47,756 | 717,139 | 204,103 |
|
Unit 2
|
56,601 | 5,883 | 50,718 | 772,319 | 194,203 |
|
Unit 3
|
55,625 | 5,882 | 49,743 | 754,030 | 184,357 |
|
Unit 4
|
185,758 | 14,442 | 171,316 | 2,315,872 | 235,081 |
|
Unit 5
|
347,815 | 26,805 | 321,010 | 4,375,618 | 237,433 |
|
Unit 6
|
291,592 | 21,970 | 269,622 | 3,653,470 | 230,550 |
|
Unit 7
|
297,385 | 23,453 | 273,932 | 3,740,810 | 214,711 |
|
Total
|
1,287,568 | 103,472 | 1,184,096 | 16,329,258 | - |
Performance Indicators in (2012)
|
Unit
|
Availability (%)
|
Unplanned outage Factor (%)
|
planned outage Factor (%)
|
Efficiency (%) Sent out
|
Heat rate (KJ/kWh)
Sent out
|
|
Unit 1
|
91.00 | 7.95 | 1.05 | 23.97 | 15,017 |
|
Unit 2
|
92.39 | 7.19 | 0.42 | 23.64 | 15,228 |
|
Unit 3
|
90.00 | 8.84 | 1.16 | 23.75 | 15,158 |
|
Unit 4
|
52.92 | 37.02 | 10.06 | 26.63 | 13,518 |
|
Unit 5
|
98.29 | 0.46 | 1.25 | 26.41 | 13,631 |
|
Unit 6
|
99.05 | 0.12 | 0.83 | 26.57 | 13,550 |
|
Unit 7
|
95.12 | 2.30 | 2.59 | 26.36 | 13,656 |
|
Total
|
87.32 | 9.60 | 3.08 | 26.10 | 13,790 |